SOLVENT-BASED SOLUTION - UP TO R 120
Fire retrofit steel structures
Reference standard: EN 13381-4/8
Fire resistance: From R 30 to R 120 – Temp. Crit. from 350° to 600°
Type of protected elements: I/H (Open profiles) and boxed profiles (square sections)
C.E. marking: ETA 15-0303
Protective system: Amotherm Steel SB – solvent-based, intumescent, 1-component paint
Consumption: Depending on the critical collapse temperature of the single element
Technical reference document: Evaluation Reports CSI 1767FR | 1801FR | 1804FR | 2285FR
Surface preparation: Compatible primers: zinc phosphate/epoxyvinyl/alkyd/alkyd epoxypolyamines with phenolic resins. In case of galvanized Steel Amotherm Steel Primer WB (0.10 kg/m2)