DOUBLE SHEET - EI 90
Fire retrofit of existing plasterboard walls
Reference standard: EN 1364-1:2015
Fire resistance: EI 90
Flame impingement: On the protected side
Wall stratigraphy: Double slab per side (2×12.5mm) with 50/600 mm C uprights
Environmental certification: Indoor Air Comfort Gold®6.0 dated 02/2017 – EPD in accordance with ISO 14025 and EN 15804
Protective system: Amotherm Gyps WB – water-based, single-component paint
Consumption: 0.80 kg/m2
Technical reference document: Classification Report I . G . 348691/3898 FR
Height in the field of direct application: 4 m
Height extension: Up to 5 m for EI 90 class – up to 12 m for EI 60 class. According to the indications of the extended application report I.G. 38021
Extension in width: Admitted
Surface preparation: Amotherm Gyps Primer WB in the ratio of 0.10 kg/m2